Range of product
|
Harmony Control Relays
|
Relay type
|
Pump control relays
|
Product or component type
|
Pump control relay
|
Product specific application
|
For 3-phase and single-phase pump
|
Relay name
|
RM35BA
|
Relay monitored parameters
|
Overcurrent and undercurrent control
Phase sequence on 3-phase supply
Phase failure on 3-phase supply
|
Time delay type
|
Adjustable 1...60 s, +/- 10 % Ti- inhibition time delay upon startup
Adjustable 0.1...10 s, +/- 10 % Tt- time delay upon fault
|
Switching capacity in VA
|
1250 VA
|
Minimum switching current
|
10 mA at 5 V DC
|
Maximum switching current
|
5 A AC/DC
|
Maximum power consumption in VA
|
5 VA AC
|
Measurement range
|
1...10 A
208...480 V AC
|
Utilisation category
|
AC-12 conforming to IEC 60947-5-1
AC-13 conforming to IEC 60947-5-1
AC-14 conforming to IEC 60947-5-1
AC-15 conforming to IEC 60947-5-1
DC-12 conforming to IEC 60947-5-1
DC-13 conforming to IEC 60947-5-1
|
Reset time
|
2000 ms
|
Maximum switching voltage
|
250 V AC/DC
|
[Un] rated nominal voltage
|
208...480 V AC 50/60 Hz, non self-powered
230 V AC 50/60 Hz, non self-powered
|
Supply voltage limits
|
183…528 V AC
|
Operating voltage tolerance
|
- 15 % + 10 % Un
|
Resistance across terminals
|
0.01 Ohm at E1-L2 terminals
|
Width
|
35 mm
|
Output contacts
|
1 C/O
|
Nominal output current
|
5 A
|
Maximum measuring cycle
|
140 ms as true rms value
|
Delay at power up
|
0.5 s
|
Hysteresis
|
5 % of threshold
|
Measurement accuracy
|
+/- 10 % of the full scale value
|
Repeat accuracy
|
+/- 1 % for input and measurement circuit
+/- 1 % for time delay
|
Measurement error
|
1 % by volt over the whole range
+/- 0.05 %/°C
|
Response time
|
< 300 ms (in the event of a fault)
|
Overload input current
|
11 A permanent at 25 °C E1-L2 terminals
50 A non repetitive < 1 s at 25 °C E1-L2 terminals
|
Marking
|
CE : EMC 89/336/EEC
CE : 73/23/EEC
|
Overvoltage category
|
III conforming to IEC 60664-1
|
Insulation resistance
|
> 500 MOhm at 500 V DC between supply and relay output conforming to 60255-5
> 500 MOhm at 500 V DC between measurement and relay output conforming to 60664-1
> 1 MOhm at 500 V DC between supply and measurement conforming to 60255-5
> 500 MOhm at 500 V DC between supply and relay output conforming to 60664-1
> 500 MOhm at 500 V DC between measurement and relay output conforming to 60255-5
> 1 MOhm at 500 V DC between supply and measurement conforming to 60664-1
|
[Ui] rated insulation voltage
|
400 V conforming to IEC 60664-1
|
Supply frequency
|
50/60 Hz +/- 10 %
|
Operating position
|
Any position
|
Connections - terminals
|
Screw terminals, 1 x 0.5...1 x 4 mm² (AWG 20...AWG 11) solid without cable end
Screw terminals, 2 x 0.5...2 x 2.5 mm² (AWG 20...AWG 14) solid without cable end
Screw terminals, 1 x 0.2...1 x 2.5 mm² (AWG 24...AWG 12) flexible with cable end
Screw terminals, 2 x 0.2...2 x 1.5 mm² (AWG 24...AWG 16) flexible with cable end
|
Tightening torque
|
0.6…1 N.m conforming to IEC 60947-1
|
Housing material
|
Self-extinguishing plastic
|
Status LED
|
1 LED green for power ON
1 LED yellow for fault
1 LED yellow for relay ON
|
Mounting support
|
35 mm symmetrical DIN rail conforming to IEC 60715
|
Electrical durability
|
100000 cycles
|
Mechanical durability
|
30000000 cycles
|
Operating rate
|
<= 360 operations/hour full load
|
Control type
|
Without test button
|
Immunity to microbreaks
|
500 ms
|
Electromagnetic compatibility
|
Emission standard for industrial environments conforming to IEC 61000-6-4
Emission standard for residential, commercial and light-industrial environments conforming to IEC 61000-6-3
Immunity for industrial environments conforming to NF EN/IEC 61000-6-2
|
Standards
|
IEC 60255-6
|
Product certifications
|
C-Tick
CSA
GOST
UL
GL
|
Ambient air temperature for storage
|
-40…70 °C
|
Ambient air temperature for operation
|
-20…50 °C
|
Relative humidity
|
95 % at 55 °C conforming to IEC 60068-2-30
|
Vibration resistance
|
0.35 mm (f= 5…57.6 Hz) conforming to IEC 60068-2-6/IEC 60255-21-1
1 gn (f= 57.6…150 Hz) conforming to IEC 60068-2-6/IEC 60255-21-1
|
Shock resistance
|
15 gn for 11 ms conforming to IEC 60255-21-1
|
IP degree of protection
|
IP20 (terminals) conforming to IEC 60529
IP30 (casing) conforming to IEC 60529
|
Pollution degree
|
3 conforming to IEC 60664-1
|
Dielectric strength
|
2 kV AC 50 Hz (shock wave 4 kV)
|
Packaging without single use plastic
|
Yes
|
Packaging made with recycled cardboard
|
Yes
|
SCIP Number
|
5e3fdf99-611b-4d07-ad17-6eba84ab488b
|
REACh Regulation
|
REACh Declaration
|
EU RoHS Directive
|
Pro-active compliance (Product out of EU RoHS legal scope)
|
Mercury free
|
Yes
|
Sustainable packaging
|
Yes
|
China RoHS Regulation
|
China RoHS declaration
|
Environmental Disclosure
|
Product Environmental Profile
|
Circularity Profile
|
End of Life Information
|
WEEE
|
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
|
California proposition 65
|
WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
|
Take-back
|
No
|
Carbon footprint (kg.eq.CO2 per CR, Total Life cycle)
|
118
|