This Application will be decommissioned as of January 7th 2025

RM35HZ21FM |
Schneider-Electric
 
RM35HZ21FM picture- web-product-data-sheet
RM35HZ21FM
frequency control relay, Harmony Control Relays, 5A, 1CO+1CO, 120…277V AC
Schneider Electric
Characteristics
Main
Range of product Harmony Control Relays
Relay type Frequency control relays
Product or component type Frequency control relay
Relay name RM35HZ21FM
Relay monitored parameters Overfrequency and underfrequency 50 or 60 Hz
Time delay type Adjustable 0.1...10 s, +/- 10 % Tt- time delay upon fault
Switching capacity in VA 1250 VA
Minimum switching current 10 mA at 5 V DC
Maximum power consumption in VA 6 VA AC
Measurement range 40...70 Hz
Utilisation category AC-12 conforming to IEC 60947-5-1
AC-13 conforming to IEC 60947-5-1
AC-14 conforming to IEC 60947-5-1
AC-15 conforming to IEC 60947-5-1
DC-12 conforming to IEC 60947-5-1
DC-13 conforming to IEC 60947-5-1
DC-14 conforming to IEC 60947-5-1
Complementary
Reset time 2000 ms time delay
Maximum switching voltage 250 V AC/DC
[Us] rated supply voltage 120...277 V AC
[Un] rated nominal voltage 120...277 V AC, non self-powered
Supply voltage limits 102…308 V AC
Control circuit frequency 40...70 Hz
Width 35 mm
Output contacts 1 C/O + 1 C/O
Contacts material Cadmium free
Nominal output current 5 A
Maximum input frequency 70 Hz
Maximum measuring cycle 200 ms measurement cycle as true rms value
Delay at power up 0.5 s
Hysteresis 0.3 % fixed
Measurement accuracy +/- 10 % of the full scale value in input
+/- 10 % of the full scale value in time delay
Repeat accuracy +/- 0.5 % for input and measurement circuit
+/- 0.5 % for time delay
Measurement error +/- 0.05 %/°C with temperature variation
< +/- 1 % over the whole range with voltage variation
Threshold setting -2...10 Hz
-10...2 Hz
Marking CE : 73/23/EEC
CE : EMC 89/336/EEC
Overvoltage category III conforming to IEC 60664-1
Insulation resistance > 500 MOhm at 500 V DC between supply and relay output conforming to IEC 60255-5
> 500 MOhm at 500 V DC between measurement and relay output conforming to IEC 60664-1
> 1 MOhm at 500 V DC between supply and measurement conforming to IEC 60255-5
> 500 MOhm at 500 V DC between supply and relay output conforming to IEC 60664-1
> 500 MOhm at 500 V DC between measurement and relay output conforming to IEC 60255-5
> 1 MOhm at 500 V DC between supply and measurement conforming to IEC 60664-1
[Ui] rated insulation voltage 400 V conforming to IEC 60664-1
Operating voltage tolerance - 15 % + 10 % Un
Supply frequency 50/60 Hz +/- 10 %
Insulation No galvanic insulation between supply and measurement
Operating position Any position without derating
Connections - terminals Screw terminals, 1 x 0.5...1 x 4 mm² (AWG 20...AWG 11) solid without cable end
Screw terminals, 2 x 0.5...2 x 2.5 mm² (AWG 20...AWG 14) solid without cable end
Screw terminals, 1 x 0.2...1 x 2.5 mm² (AWG 24...AWG 12) flexible with cable end
Screw terminals, 2 x 0.2...2 x 1.5 mm² (AWG 24...AWG 16) flexible with cable end
Tightening torque 0.6…1 N.m conforming to IEC 60947-1
Housing material Self-extinguishing plastic
Local signalling 1 LED green for power ON
1 LED yellow for correct frequency (high R1)
1 LED yellow for correct frequency (low R2)
Mounting support 35 mm symmetrical DIN rail conforming to IEC 60715
Electrical durability 100000 cycles
Mechanical durability 30000000 cycles
Operating rate <= 360 operations/hour full load
Control type Without test button
Environment
Immunity to microbreaks 10 ms
Electromagnetic compatibility Emission standard for industrial environments conforming to IEC 61000-6-4
Emission standard for residential, commercial and light-industrial environments conforming to IEC 61000-6-3
Immunity for industrial environments conforming to NF EN/IEC 61000-6-2
Standards IEC 60255-6
NF EN 60255-6
Product certifications GL
UL
CSA
C-Tick
GOST
Ambient air temperature for storage -40…70 °C
Ambient air temperature for operation -20…50 °C
Relative humidity 95 % at 55 °C conforming to IEC 60068-2-30
Vibration resistance 0.35 mm (f= 5…57.6 Hz) conforming to IEC 60068-2-6/IEC 60255-21-1
1 gn (f= 57.6…150 Hz) conforming to IEC 60068-2-6/IEC 60255-21-1
Shock resistance 15 gn for 11 ms conforming to IEC 60255-21-1
IP degree of protection IP20 (terminals) conforming to IEC 60529
IP30 (casing) conforming to IEC 60529
Pollution degree 3 conforming to IEC 60664-1
Dielectric test voltage 2 kV AC 50 Hz
Non-dissipating shock wave 4 kV
Packing Units
Unit Type of Package 1 PCE
Number of Units in Package 1 1
Package 1 Height 4.600 cm
Package 1 Width 8.000 cm
Package 1 Length 9.700 cm
Package 1 Weight 126.000 g
Unit Type of Package 2 S03
Number of Units in Package 2 48
Package 2 Height 30.000 cm
Package 2 Width 30.000 cm
Package 2 Length 40.000 cm
Package 2 Weight 6.838 kg
Offer Sustainability
Packaging without single use plastic Yes
Packaging made with recycled cardboard Yes
REACh Regulation
print REACh Declaration
EU RoHS Directive Pro-active compliance (Product out of EU RoHS legal scope)
Mercury free Yes
Sustainable packaging Yes
China RoHS Regulation
print China RoHS declaration
Environmental Disclosure
print Product Environmental Profile
Circularity Profile
print End of Life Information
California proposition 65 WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
Take-back No
Carbon footprint (kg.eq.CO2 per CR, Total Life cycle) 35
Contractual warranty
Warranty 18 months