Range of product
|
Harmony Control Relays
|
Relay type
|
Speed control relays
|
Product or component type
|
Speed control relay
|
Relay name
|
RM35S
|
Relay monitored parameters
|
Overspeed
Underspeed
|
Time delay range
|
0.6...60 s adjustable on energisation delay (tolerance: 0...10 % of the full scale value)
|
Switching capacity in VA
|
1250 VA
|
Minimum switching current
|
10 mA at 5 V DC
|
Maximum power consumption in VA
|
5 VA AC
|
Measurement range
|
0.05...0.5 s
0.5...5 min
1...10 min
1...10 s
0.5...5 s
0.1...1 s
0.1...1 min
|
Utilisation category
|
AC-12 conforming to IEC 60947-5-1
AC-13 conforming to IEC 60947-5-1
AC-14 conforming to IEC 60947-5-1
AC-15 conforming to IEC 60947-5-1
DC-12 conforming to IEC 60947-5-1
DC-13 conforming to IEC 60947-5-1
DC-14 conforming to IEC 60947-5-1
|
Measurement range
|
0.05...600 s
|
Time delay
|
Adjustable 0.6...60 s Ti- inhibition time delay upon startup
|
Rest time in memory mode
|
50 ms contact S2 in memory mode on time delay
1 s supply Un in memory mode on time delay
|
Maximum switching voltage
|
250 V AC/DC
|
[Un] rated nominal voltage
|
24...240 V AC/DC 50/60 Hz, non self-powered
|
Supply voltage limits
|
20.4…264 V AC/DC
|
Maximum power consumption in W
|
3 W DC
|
Width
|
35 mm
|
Output contacts
|
1 C/O
|
Contacts material
|
Cadmium free
|
Nominal output current
|
5 A
|
Delay at power up
|
0.05 s
|
Hysteresis
|
5 % of threshold
|
Measurement accuracy
|
+/- 10 % of the full scale value
|
Repeat accuracy
|
+/- 0.5 % for input and measurement circuit
+/- 0.5 % for time delay
|
Measurement error
|
+/- 0.1 %/°C with temperature variation
< +/- 1 % over the whole range with voltage variation
|
Input frequency
|
0.0017…20 Hz
|
Response time
|
15 ms max (on crossing the threshold)
|
Polarity
|
Reversible polarity on DC supply
|
Threshold setting
|
10...100 %
|
Supply voltage for sensor
|
11.5...12.5 V
|
Maximum supply current for sensors
|
40 mA for < 24 V AC at 25 °C
40 mA for < 24 V DC at 25 °C
50 mA for 24...240 V AC
50 mA for 24...240 V DC
|
Impulse duration
|
>= 5 ms high state
>= 5 ms low state
|
Input compatibility
|
3-wire sensor (E1) PNP or NPN, 12 V, 50 mA
NAMUR sensor (E2), 12 V, 1.5 kOhm
Voltage input (E1), 0...30 V, 9.5 kOhm, high state >= 4.5 V low state <= 1 V
Volt-free contact input (E1), 12 V, 9.5 kOhm
|
Marking
|
CE : EMC 89/336/EEC
CE : 73/23/EEC
|
Overvoltage category
|
III conforming to IEC 60664-1
|
Insulation resistance
|
> 500 MOhm at 500 V DC between supply and relay output conforming to IEC 60255-5
> 500 MOhm at 500 V DC between measurement and relay output conforming to IEC 60664-1
> 1 MOhm at 500 V DC between supply and measurement conforming to IEC 60255-5
> 500 MOhm at 500 V DC between supply and relay output conforming to IEC 60664-1
> 500 MOhm at 500 V DC between measurement and relay output conforming to IEC 60255-5
> 1 MOhm at 500 V DC between supply and measurement conforming to IEC 60664-1
|
[Ui] rated insulation voltage
|
250 V conforming to IEC 60664-1
|
Operating voltage tolerance
|
- 15 % + 10 % Un
|
Supply frequency
|
50/60 Hz +/- 10 %
|
Operating position
|
Any position without derating
|
Connections - terminals
|
Screw terminals, 1 x 0.5...1 x 4 mm² (AWG 20...AWG 11) solid without cable end
Screw terminals, 2 x 0.5...2 x 2.5 mm² (AWG 20...AWG 14) solid without cable end
Screw terminals, 1 x 0.2...1 x 2.5 mm² (AWG 24...AWG 12) flexible with cable end
Screw terminals, 2 x 0.2...2 x 1.5 mm² (AWG 24...AWG 16) flexible with cable end
|
Tightening torque
|
0.6…1 N.m conforming to IEC 60947-1
|
Housing material
|
Self-extinguishing plastic
|
Status LED
|
1 LED green for power ON
1 LED yellow for inhibit
1 LED yellow for relay (R)
|
Mounting support
|
35 mm symmetrical DIN rail conforming to IEC 60715
|
Electrical durability
|
100000 cycles
|
Mechanical durability
|
30000000 cycles
|
Operating rate
|
<= 360 operations/hour full load
|
Control type
|
Without test button
|
Immunity to microbreaks
|
50 ms
|
Electromagnetic compatibility
|
Emission standard for industrial environments conforming to IEC 61000-6-4
Emission standard for residential, commercial and light-industrial environments conforming to IEC 61000-6-3
Immunity for industrial environments conforming to NF EN/IEC 61000-6-2
|
Standards
|
NF EN 60255-6
IEC 60255-6
|
Product certifications
|
C-Tick
GOST
UL
GL
CSA
|
Ambient air temperature for storage
|
-40…70 °C
|
Ambient air temperature for operation
|
-20…50 °C
|
Relative humidity
|
95 % at 55 °C conforming to IEC 60068-2-30
|
Vibration resistance
|
0.35 mm (f= 5…57.6 Hz) conforming to IEC 60068-2-6/IEC 60255-21-1
1 gn (f= 57.6…150 Hz) conforming to IEC 60068-2-6/IEC 60255-21-1
|
Shock resistance
|
15 gn for 11 ms conforming to IEC 60255-21-1
|
IP degree of protection
|
IP20 (terminals) conforming to IEC 60529
IP30 (casing) conforming to IEC 60529
|
Pollution degree
|
3 conforming to IEC 60664-1
|
Dielectric test voltage
|
2 kV AC 50 Hz
|
Non-dissipating shock wave
|
4 kV
|