[Un] rated nominal voltage
|
24...240 V AC/DC 50/60 Hz, non self-powered
|
Supply voltage limits
|
20.4…264 V AC
20.4…264 V DC
|
Reset time
|
10000 ms output
|
Maximum switching voltage
|
250 V AC
250 V DC
|
Switching capacity in VA
|
1250 VA
|
Minimum switching current
|
10 mA at 5 V DC
|
Maximum switching current
|
5 A AC
5 A DC
|
Power consumption in VA
|
0…4 VA at 24...240 V AC
|
Power consumption
|
0.5 W DC
|
Control circuit frequency
|
50...60 Hz +/- 10 %
|
Resistance across terminals
|
602 mOhm
|
Measurement voltage limits
|
176…528 V AC
|
Delay at power up
|
500 ms
|
Voltage range
|
176...528 V
|
Response time
|
> 50 ms (input Y1 (contact Y1-T1) and push-button)
|
[Uc] control circuit voltage
|
<= 3.6 V of temperature control circuit (T1-T2 terminals open)
|
Short-circuit current
|
0.007 A temperature sensing circuit (T1-T2 terminals short circuited)
|
Maximum resistance
|
1500 Ohm for temperature sensor at 20 °C
|
Tripping threshold
|
3100 Ohm +/- 10 % for temperature control circuit
|
Reset threshold
|
1650 Ohm +/- 10 % for temperature control circuit
|
Insulation resistance
|
> 500 MOhm at 500 V DC between supply and relay output conforming to IEC 60255-5
> 500 MOhm at 500 V DC between measurement and relay output conforming to IEC 60664-1
> 1 MOhm at 500 V DC between supply and measurement conforming to IEC 60255-5
> 500 MOhm at 500 V DC between supply and relay output conforming to IEC 60664-1
> 500 MOhm at 500 V DC between measurement and relay output conforming to IEC 60255-5
> 1 MOhm at 500 V DC between supply and measurement conforming to IEC 60664-1
|
[Ui] rated insulation voltage
|
400 V conforming to IEC 60664-1
|
Supply frequency
|
50/60 Hz +/- 10 %
|
Operating position
|
Any position without derating
|
Connections - terminals
|
Screw terminals, 1 x 0.5...1 x 4 mm² (AWG 20...AWG 11) solid without cable end
Screw terminals, 2 x 0.5...2 x 2.5 mm² (AWG 20...AWG 14) solid without cable end
Screw terminals, 1 x 0.2...1 x 2.5 mm² (AWG 24...AWG 12) flexible with cable end
Screw terminals, 2 x 0.2...2 x 1.5 mm² (AWG 24...AWG 16) flexible with cable end
|
Tightening torque
|
0.6…1 N.m conforming to IEC 60947-1
|
Housing material
|
Self-extinguishing plastic
|
Local signalling
|
LED (green) for power ON
LED (yellow) for phase of relay (R2)
LED (yellow) for temperature of relay (R1)
|
Mounting support
|
35 mm symmetrical DIN rail conforming to IEC 60715
|
Electrical durability
|
10000 cycles
|
Mechanical durability
|
30000000 cycles
|
Operating rate
|
<= 360 operations/hour full load
|
Utilisation category
|
AC-12 conforming to IEC 60947-5-1
AC-13 conforming to IEC 60947-5-1
AC-14 conforming to IEC 60947-5-1
AC-15 conforming to IEC 60947-5-1
DC-12 conforming to IEC 60947-5-1
DC-13 conforming to IEC 60947-5-1
|
Width
|
35 mm
|
Net weight
|
0.13 kg
|
Control type
|
With test button
|
Immunity to microbreaks
|
20 ms at 20.4 V
|
Electromagnetic compatibility
|
Emission standard for industrial environments conforming to IEC 61000-6-4
Emission standard for residential, commercial and light-industrial environments conforming to IEC 61000-6-3
Immunity for industrial environments conforming to IEC 61000-6-2
|
Standards
|
IEC 60255-6
IEC 60034-11-2
|
Product certifications
|
CSA
C-Tick
GOST
UL
GL
|
Marking
|
CE
|
Directives
|
73/23/EEC - low voltage directive
89/336/EEC - electromagnetic compatibility
|
Ambient air temperature for storage
|
-40…70 °C
|
Ambient air temperature for operation
|
-20…50 °C
|
Relative humidity
|
95 % at 55 °C conforming to IEC 60068-2-30
|
Vibration resistance
|
0.35 mm (f= 5…57.6 Hz) conforming to IEC 60068-2-6
1 gn (f= 57.6…150 Hz) conforming to IEC 60255-21-1
|
Shock resistance
|
15 gn for 11 ms conforming to IEC 60255-21-1
|
IP degree of protection
|
IP20 (terminals) conforming to IEC 60529
IP30 (casing) conforming to IEC 60529
|
Pollution degree
|
3 conforming to IEC 60664-1
|
Overvoltage category
|
III conforming to IEC 60664-1
|
Dielectric test voltage
|
2 kV, 1 min AC 50 Hz
|
Non-dissipating shock wave
|
4 kV
|