Protection type
|
Reverse polarity protection on output
Short-circuit protection on output
Overvoltage protection on output (+/- 30 V)
|
Abnormal analogue output voltage
|
11...15 V, output selected - 10...10 V no input or input wire broken voltage
11...15 V, output selected 0...10 V no input or input wire broken voltage
-15...0 V, output selected 0...20 mA no input or input wire broken current
-15...0 V, output selected 4...20 mA no input or input wire broken current
|
Abnormal analogue output current
|
22…30 mA, output selected 0...20 mA no input or input wire broken voltage
22…30 mA, output selected 4...20 mA no input or input wire broken voltage
-30…0 mA, output selected 0...20 mA no input or input wire broken current
4…30 mA, output selected 4...20 mA no input or input wire broken current
|
[Us] rated supply voltage
|
24 V DC +/- 20 %, isolated
|
Current consumption
|
<= 70 mA for voltage output
<= 90 mA for current output
|
Local signalling
|
LED (green) for power ON
|
Measurement error
|
+/- 5 % of full scale at 20 °C (temporary performance degradation when subject to electromagnetic interference)
|
Repeat accuracy
|
+/- 0.2 % full scale at 20 °C
+/- 0.6 % full scale at 60 °C
|
Temperature coefficient
|
200 ppm/°C
|
Clamping connection capacity
|
2 x 1.5 mm²
1 x 2.5 mm²
|
Tightening torque
|
0.6…1.1 N.m
|
Marking
|
CE
|
Surge withstand
|
0.5 kV during 1.2/50 µs conforming to IEC 61000-4-5
|
[Ui] rated insulation voltage
|
2 kV
|
Fixing mode
|
By screws (mounting plate)
Clip-on (35 mm symmetrical DIN rail)
|
Safety reliability data
|
B10d = 20000
MTTFd = 21.6 years
|
Net weight
|
0.12 kg
|
Standards
|
IEC 60947-1
IEC 60584-1
|
Product certifications
|
UL
GL
CSA
|
IP degree of protection
|
IP20 (terminal block)
IP50 (housing)
|
Fire resistance
|
850 °C conforming to IEC 60695-2-1
850 °C conforming to UL
|
Shock resistance
|
50 gn for 11 ms conforming to IEC 60068-2-27
|
Vibration resistance
|
5 gn (f= 10…100 Hz) conforming to IEC 60068-2-6
|
Resistance to electrostatic discharge
|
6 kV (in contact) conforming to IEC 61000-4-2 level 3
8 kV (in air) conforming to IEC 61000-4-2 level 3
|
Resistance to fast transients
|
1 kV (on input-output) conforming to IEC 61000-4-4
2 kV (on power supply) conforming to IEC 61000-4-4
|
Disturbance radiated/conducted
|
CISPR 22 group 1 - class B
CISPR 11
|
Ambient air temperature for storage
|
-40…85 °C
|
Ambient air temperature for operation
|
0…50 °C mounting side by side
0…60 °C 2 cm spacing
|
Pollution degree
|
2 conforming to IEC 60664-1
|