Fixing mode
|
Plastic compression spring
|
Average resistance
|
20500 Ohm network: DC at 23 °C +/- 10 %
|
[Ui] rated insulation voltage
|
250 V conforming to IEC
277 V conforming to cUL
|
[Uimp] rated impulse withstand voltage
|
6 kV conforming to IEC
|
Contacts material
|
Silver alloy (AgSnO2)
|
[Ie] rated operational current
|
6 A 1 C/O (AC-1/DC-1) conforming to IEC/UL
|
Minimum switching current
|
100 mA
|
Maximum switching voltage
|
277 V
|
Minimum switching voltage
|
12 V
|
Maximum switching capacity
|
1500 VA
150 W
|
Minimum switching capacity
|
120 mW
|
Operating rate
|
<= 72000 cycles/hour no-load
<= 360 cycles/hour under load
|
Mechanical durability
|
10000000 cycles
|
Electrical durability
|
60000 cycles for resistive load, 6 A at 250 V, AC-1
|
Operating time
|
5 ms reset
12 ms
|
Reset time
|
20 ms
|
Marking
|
CE
|
Protection category
|
RT III
|
Test levels
|
Level A group mounting
|
Operating position
|
Any position
|
Height
|
78.6 mm
|
Width
|
6.2 mm
|
Depth
|
101 mm
|
Terminals description ISO n°1
|
(A1-A2)CO
(11-12-14)OC
|
Sale per indivisible quantity
|
10
|
Net weight
|
0.029 kg
|
Load current
|
6 A at 250 V AC 0.5 mm mounting distance
|
Average coil consumption
|
0.17 W, DC
|
Drop-out voltage threshold
|
>= 0.05 Uc
|
Contact terminal arrangement
|
Separate
|
Connections - terminals
|
Spring terminals, 1 x 0.2...1 x 1.5 mm² (AWG 24...AWG 16) flexible with cable end
Spring terminals, 1 x 0.2...1 x 1.5 mm² (AWG 24...AWG 16) solid without cable end
|
Safety reliability data
|
B10d = 60000
|
Clamping force
|
10…40 N
|
Control type
|
Without push-button
|
Mounting support
|
35 mm symmetrical DIN rail
|
Device presentation
|
Complete product
|
Input voltage
|
230 V AC/DC (input voltage limit: 184...264.5 V)
|
Dielectric strength
|
1000 V AC between contacts
4000 V AC between coil and contact
|
Standards
|
CSA C22.2 No 14
IEC 61810-1
UL 508
|
Product certifications
|
GOST
CSA
UL
|
Ambient air temperature for storage
|
-40…85 °C
|
Vibration resistance
|
10 gn, amplitude = +/- 1 mm (f = 10…150 Hz)10 cycles not operating conforming to IEC 60068-2-6
5 gn, amplitude = +/- 1 mm (f = 10…150 Hz)10 cycles in operation conforming to IEC 60068-2-6
|
IP degree of protection
|
IP40 conforming to IEC 60529
|
Shock resistance
|
10 gn (duration = 11 ms) for in operation conforming to IEC 60068-2-27
5 gn (duration = 11 ms) for not operating conforming to IEC 60068-2-27
|
Ambient air temperature for operation
|
-40…70 °C
|