Test button
|
With test button
|
[Uc] control circuit voltage
|
4...32 V DC
|
Minimum switching voltage
|
4 V DC turn-on
|
Maximum switching voltage
|
1 V DC turn-off
|
Response time
|
0.5 cycle (turn-on)
0.5 cycle (turn-off)
|
Input current
|
7…12 mA
|
Output voltage
|
48...660 V AC
|
Load current
|
0.15…75 A
|
Transient overvoltage
|
1200 V
|
Surge current
|
1000 A for 16.6 ms
|
Maximum I²t for fusing
|
4150 A².s for 8.33 ms at 60 Hz
4555 A².s for 10 ms at 50 Hz
|
Co-ordination type
|
Type 1 - 50 A miniature circuit breaker (MCB) - curve B
Type 2 - 40 A miniature circuit breaker (MCB) - curve B
|
Maximum leakage current
|
1 mA off-state
|
Maximum voltage drop
|
<1.15 V on-state
|
DV/dt
|
500 V/µs off-state at maximum voltage
|
Power factor
|
0.5 (with maximum load)
|
Motor controller rating
|
1.5 hp 120 V AC
3 hp 240 V AC
7.5 hp 480 V AC
|
Insulation resistance
|
1000 MOhm at 500 V DC
|
Maximum capacitance
|
8 pF for input/output
|
Dielectric strength
|
4 kV AC for input/output
4 kV AC for input or output to case
|
[Uimp] rated impulse withstand voltage
|
6 kV output to case
6 kV input to output
|
Tightening torque
|
1.5...1.7 N.m for input
2...2.2 N.m for output
17.7...19.47 lb.in for output
13.27...15.04 lb.in for input
0.5...0.6 N.m for auxillary terminal
4.4...5.3 lb.in for auxillary terminal
|
Connections - terminals
|
Screw terminals: 0.2...3.3 mm², (AWG 24...AWG 12) with cable end for input
Screw terminals: 0.5...5.26 mm², (AWG 20...AWG 10) with cable end for output
Screw terminals: 0.2...3.3 mm², (AWG 24...AWG 12) without cable end for input
Screw terminals: 0.5...8.26 mm², (AWG 20...AWG 8) without cable end for output
Forked type tag connectors: 9.2 x 4 mm for input
Ring lugs: 9.2 x 4 mm for input
Forked type tag connectors: 11.7 x 4.5 mm for output
Ring lugs: 11.7 x 4.5 mm for output
|
Auxiliary/Alarm connection terminal
|
Screw-type connector, 0.5...1.5 mm² (AWG 20...AWG 16) with slotted Philips screwdriver
|
Thermal resistance
|
0.3 °C/W junction to case
|
LED indicator
|
LED, steady, green for ON status for control input/test button actuated
LED, steady, amber for ON status for load
LED, flashing, amber for control input to energise load
LED, steady, red for open-circuit for control input
LED, flashing, red for load cut-off/short-circuit
|
Maximum alarm output current
|
30 mA at 32 V DC
|
Minimum load current
|
150 mA
|
IP degree of protection
|
IP20
|
Electromagnetic compatibility
|
Electrostatic discharge 6 kV criteria A contact discharge conforming to IEC 61000-4-2
Electrostatic discharge 8 kV criteria A air discharge conforming to IEC 61000-4-2
Radiated radio-frequency electromagnetic field immunity test criteria A output ports conforming to IEC 61000-4-3
Radiated radio-frequency electromagnetic field immunity test criteria B alarm port conforming to IEC 61000-4-3
Electrical fast transient/burst immunity test 1 kV, 5/100 kHz criteria B output ports conforming to IEC 61000-4-4
Surge immunity test 1 kV criteria A output ports line to line conforming to IEC 61000-4-5
Surge immunity test 2 kV criteria A output ports line to earth conforming to IEC 61000-4-5
|
Safety reliability data
|
B10d = 1731395
MTTFd = 1875.9 years
|
Net weight
|
97.1 g
|
Device presentation
|
Complete product
|
Packaging without single use plastic
|
Yes
|
Packaging made with recycled cardboard
|
No
|
SCIP Number
|
134201bc-d293-4667-9cca-10a7f11729e0
|
REACh Regulation
|
REACh Declaration
|
EU RoHS Directive
|
Pro-active compliance (Product out of EU RoHS legal scope)
|
Mercury free
|
Yes
|
RoHS exemption information
|
Yes
|
China RoHS Regulation
|
China RoHS declaration
|
Environmental Disclosure
|
Product Environmental Profile
|
Circularity Profile
|
End of Life Information
|
California proposition 65
|
WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
|
Take-back
|
No
|
Carbon footprint (kg.eq.CO2 per CR, Total Life cycle)
|
7828
|