STBAVI0300K
analog input kit, Modicon STB, standard, +/- 10V, 4 I, 15bits with sign
|
|
|
Main
Range of product
|
Modicon STB distributed I/O solution
|
Product or component type
|
Standard analog input kit
|
Kit composition
|
STBAVI0300 module
STBXTS1100, 6-terminal screw type connector
STBXTS2100, 6-terminal spring clamp connector
STBXBA1000 base
|
Analogue input type
|
Voltage +/- 10 V
Voltage +/- 5 V
Voltage 0...10 V
Voltage 0...5 V
Voltage 1...5 V
|
Analogue input number
|
4
|
Analogue input resolution
|
15 bits + sign
|
Type of filter
|
Single low pass input filter 25 Hz
|
Complementary
Absolute maximum input
|
50 V DC
|
Cold swapping
|
Yes
|
Hot swapping fallback
|
Yes for standard NIMs
|
Fallback status
|
State 0 basic NIMs
User configurable standard NIMs
|
Data format
|
EN 61131-2
IEC 61131-2
|
Integral linearity
|
+/- 0.2 %FS
|
Differential linearity
|
Monotonic
|
Input impedance
|
400 kOhm
|
Maximum supply current for sensors
|
100 mA per input channels
|
Maximum source impedance
|
1 kOhm
|
Absolute accuracy error
|
+/- 0.75 % of full scale 25 °C
|
Temperature drift
|
+/-0.01 %/°C
|
Insulation between channels and logic bus
|
1500 V for 1 minute
|
Insulation between channels and sensor bus
|
30 V
|
Addressing requirement
|
2 input words
|
Product compatibility
|
Mounting base STBXBA1000
Power distribution module STBPDT3100/3105
|
[Us] rated supply voltage
|
24 V DC
|
Supply
|
Power distribution module
|
Current consumption
|
90 mA at 5 V DC for logic bus
|
Marking
|
CE
|
Overvoltage category
|
II
|
Status LED
|
1 LED (green) module status (RDY)
1 LED (red) module error (ERR)
|
Environment
Product certifications
|
FM Class 1 Division 2
UL
CSA
ATEX Cat 3G
C-Tick
|
Pollution degree
|
2 conforming to IEC 60664-1
|
Operating altitude
|
<= 2000 m
|
IP degree of protection
|
IP20 conforming to IEC 61131-2 class 1
|
Ambient air temperature for operation
|
-25…70 °C
|
Ambient air temperature for operation
|
- 13...158 °F without derating
|
Ambient air temperature for storage
|
-40…85 °C without derating
|
Ambient air temperature for storage
|
-40...185 °F without derating
|
Relative humidity
|
95 % at 60 °C without condensation
|
Vibration resistance
|
+/-0.35 mm at 10…58 Hz
3 gn at 58…150 Hz on 35 x 7.5 mm symmetrical DIN rail
5 gn at 58…150 Hz on 35 x 15 mm symmetrical DIN rail
|
Shock resistance
|
30 gn for 11 ms conforming to IEC 88 reference 2-27
|
Packing Units
Unit Type of Package 1
|
PCE
|
Number of Units in Package 1
|
1
|
Package 1 Height
|
3.0 cm
|
Package 1 Width
|
8.0 cm
|
Package 1 Length
|
13.0 cm
|
Package 1 Weight
|
149.0 g
|
Unit Type of Package 2
|
S02
|
Number of Units in Package 2
|
28
|
Package 2 Height
|
15.0 cm
|
Package 2 Width
|
30.0 cm
|
Package 2 Length
|
40.0 cm
|
Package 2 Weight
|
4.598 kg
|
Unit Type of Package 3
|
PAL
|
Number of Units in Package 3
|
448
|
Package 3 Height
|
60.0 cm
|
Package 3 Width
|
80.0 cm
|
Package 3 Length
|
448.0 cm
|
Package 3 Weight
|
66.752 kg
|
Offer Sustainability
Packaging without single use plastic
|
No
|
Packaging made with recycled cardboard
|
No
|
SCIP Number
|
6830dd70-e4bc-47df-85c7-e41f888576f4
|
REACh Regulation
|
REACh Declaration
|
EU RoHS Directive
|
Pro-active compliance (Product out of EU RoHS legal scope)
|
Mercury free
|
Yes
|
RoHS exemption information
|
Yes
|
China RoHS Regulation
|
China RoHS declaration
|
WEEE
|
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
|
California proposition 65
|
WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
|
Take-back
|
No
|
Carbon footprint (kg.eq.CO2 per CR, Total Life cycle)
|
29
|
Contractual warranty
|
|