Input voltage limits
|
0...40 V at state 0
159...256 V at state 1
|
Permissible voltage
|
265 V
|
Absolute maximum voltage
|
400 V 20 ms
|
Network frequency
|
50/60 Hz
|
Network frequency limits
|
47…63 Hz
|
Current state 0 guaranteed
|
<= 2 mA
|
Current state 1 guaranteed
|
>= 4 mA
|
Response time
|
1.5 ms off-to-on
1.5 ms on-to-off
|
Protection type
|
Power protection integrated fuse on PDM time lag 10 A
Input protection resistor-limited
|
Insulation between channels and logic bus
|
1780 V for 1 minute
|
Cold swapping
|
Yes
|
Hot swapping
|
Yes for standard NIMs
|
Product compatibility
|
Power distribution module STBPDT2100/2105
I/O base STBXBA2000
|
[Us] rated supply voltage
|
115/230 V AC
|
Supply
|
Power distribution module
|
Current consumption
|
40 mA at 5 V DC for logic bus
|
Marking
|
CE
|
Overvoltage category
|
II
|
Status LED
|
1 LED (green) module status (RDY)
1 LED per channel (green) channel status (IN1 to IN2)
1 LED (red) module error (ERR)
|
Depth
|
65.1 mm
|
Height
|
18.4 mm
|
Width
|
125 mm
|
Net weight
|
0.122 kg
|
Standards
|
EN/IEC 61131-2 type 1
|
Product certifications
|
CSA
UL
FM Class 1 Division 2
|
Pollution degree
|
2 conforming to IEC 60664-1
|
Operating altitude
|
<= 2000 m
|
IP degree of protection
|
IP20 conforming to IEC 61131-2 class 1
|
Ambient air temperature for operation
|
0…60 °C (without derating)
|
Ambient air temperature for operation
|
32...140 °F without derating
|
Ambient air temperature for storage
|
-40…85 °C without derating
|
Ambient air temperature for storage
|
-40...185 °F without derating
|
Relative humidity
|
95 % at 60 °C without condensation
|
Vibration resistance
|
3 gn at 58…150 Hz on 35 x 7.5 mm symmetrical DIN rail
5 gn at 58…150 Hz on 35 x 15 mm symmetrical DIN rail
+/-0.35 mm at 10…58 Hz
|
Shock resistance
|
30 gn for 11 ms conforming to IEC 88 reference 2-27
|