Discrete I/O number
|
40
|
Maximum number of I/O expansion module
|
7 (local I/O-Architecture)
14 (remote I/O-Architecture)
|
Supply voltage limits
|
85…264 V
|
Network frequency
|
50/60 Hz
|
Discrete input logic
|
Sink or source
|
Discrete input voltage
|
24 V
|
Discrete input voltage type
|
DC
|
Voltage state 1 guaranteed
|
>= 15 V for input
|
Voltage state 0 guaranteed
|
<= 5 V for input
|
Discrete input current
|
7 mA for input
|
Input impedance
|
4.7 kOhm for input
|
Response time
|
50 µs turn-on, I0...I15 terminal(s) for input
|
Configurable filtering time
|
1 µs for fast input
|
Discrete output logic
|
Positive logic (source)
|
Output voltage limits
|
125 V DC relay output
30 V DC transistor output
277 V AC relay output
|
Maximum output frequency
|
1 kHz for transistor output
20 kHz for fast output (PWM mode)
100 kHz for fast output (PLS mode)
|
Accuracy
|
+/- 0.1 % at 0.02…0.1 kHz for fast output
|
Protection type
|
Short-circuit protection for transistor output
Short-circuit and overload protection with automatic reset for transistor output
Reverse polarity protection for transistor output
Without protection for relay output
|
Reset time
|
10 ms automatic reset output
12 s automatic reset fast output
|
Memory capacity
|
64 MB for system memory RAM
|
Data backed up
|
128 MB built-in flash memory for backup of user programs
|
Data storage equipment
|
<= 16 GB SD card (optional)
|
Battery type
|
BR2032 lithium non-rechargeable, battery life: 4 year(s)
|
Backup time
|
2 years at 25 °C
|
Execution time for 1 KInstruction
|
0.3 ms for event and periodic task
0.7 ms for other instruction
|
Application structure
|
4 cyclic master tasks
3 cyclic master tasks + 1 freewheeling task
8 external event tasks
8 event tasks
|
Realtime clock
|
With
|
Clock drift
|
<= 60 s/month at 25 °C
|
Positioning functions
|
PTO function 4 channel(s) (positioning frequency: 100 kHz)
|
Counting input number
|
4 fast input (HSC mode) at 200 kHz
14 standard input at 1 kHz
|
Control signal type
|
A/B at 100 kHz for fast input (HSC mode)
Pulse/direction at 200 kHz for fast input (HSC mode)
Single phase at 200 kHz for fast input (HSC mode)
|
Integrated connection type
|
Non isolated serial link serial 1 with RJ45 connector and RS232/RS485 interface
Non isolated serial link serial 2 with removable screw terminal block connector and RS485 interface
USB port with mini B USB 2.0 connector
|
Supply
|
(serial 1)serial link supply: 5 V, <200 mA
|
Transmission rate
|
1.2...115.2 kbit/s (115.2 kbit/s by default) for bus length of 15 m for RS485
1.2...115.2 kbit/s (115.2 kbit/s by default) for bus length of 3 m for RS232
480 Mbit/s for bus length of 3 m for USB
|
Communication port protocol
|
Non isolated serial link: Modbus master/slave
|
Local signalling
|
1 LED (green) for PWR
1 LED (green) for RUN
1 LED (red) for module error (ERR)
1 LED (red) for I/O error (I/O)
1 LED (green) for SD card access (SD)
1 LED (red) for BAT
1 LED (green) for SL1
1 LED (green) for SL2
1 LED (red) for bus fault on TM4 (TM4)
1 LED per channel (green) for I/O state
|
Electrical connection
|
Removable screw terminal blockfor inputs and outputs (pitch 5.08 mm)
Removable screw terminal blockfor connecting the 24 V DC power supply (pitch 5.08 mm)
|
Maximum cable distance between devices
|
Unshielded cable: <50 m for input
Shielded cable: <10 m for fast input
Unshielded cable: <50 m for output
Shielded cable: <3 m for fast output
|
Insulation
|
Between supply and internal logic at 500 V AC
Non-insulated between supply and ground
|
Marking
|
CE
|
Sensor power supply
|
24 V DC at 400 mA supplied by the controller
|
Surge withstand
|
2 kV power lines (AC) common mode conforming to IEC 61000-4-5
2 kV relay output common mode conforming to IEC 61000-4-5
1 kV shielded cable common mode conforming to IEC 61000-4-5
1 kV power lines (AC) differential mode conforming to IEC 61000-4-5
1 kV relay output differential mode conforming to IEC 61000-4-5
1 kV input common mode conforming to IEC 61000-4-5
1 kV transistor output common mode conforming to IEC 61000-4-5
|
Mounting support
|
Top hat type TH35-15 rail conforming to IEC 60715
Top hat type TH35-7.5 rail conforming to IEC 60715
Plate or panel with fixing kit
|
Height
|
90 mm
|
Depth
|
95 mm
|
Width
|
190 mm
|
Net weight
|
0.62 kg
|
Standards
|
ANSI/ISA 12-12-01
CSA C22.2 No 142
CSA C22.2 No 213
IEC 61131-2:2007
Marine specification (LR, ABS, DNV, GL)
UL 508
|
Product certifications
|
RCM
cULus
CE
UKCA
DNV-GL
ABS
LR
|
Resistance to electrostatic discharge
|
8 kV in air conforming to IEC 61000-4-2
4 kV on contact conforming to IEC 61000-4-2
|
Resistance to electromagnetic fields
|
10 V/m 80 MHz...1 GHz conforming to IEC 61000-4-3
3 V/m 1.4 GHz...2 GHz conforming to IEC 61000-4-3
1 V/m 2 GHz...3 GHz conforming to IEC 61000-4-3
|
Resistance to fast transients
|
2 kV (power lines) conforming to IEC 61000-4-4
2 kV (relay output) conforming to IEC 61000-4-4
1 kV (serial link) conforming to IEC 61000-4-4
1 kV (input) conforming to IEC 61000-4-4
1 kV (transistor output) conforming to IEC 61000-4-4
|
Resistance to conducted disturbances
|
10 V 0.15...80 MHz conforming to IEC 61000-4-6
3 V 0.1...80 MHz conforming to Marine specification (LR, ABS, DNV, GL)
10 V spot frequency (2, 3, 4, 6.2, 8.2, 12.6, 16.5, 18.8, 22, 25 MHz) conforming to Marine specification (LR, ABS, DNV, GL)
|
Electromagnetic emission
|
Conducted emissions - test level: 120...69 dBµV/m QP ( power lines) at 10…150 kHz conforming to IEC 55011
Conducted emissions - test level: 63 dBμV/m QP ( power lines) at 1.5…30 MHz conforming to IEC 55011
Conducted emissions - test level: 79 dBμV/m QP/66 dBμV/m AV ( power lines) at 0.15…0.5 MHz conforming to IEC 55011
Conducted emissions - test level: 73 dBμV/m QP/60 dBμV/m AV ( power lines) at 0.5…300 MHz conforming to IEC 55011
Radiated emissions - test level: 40 dBμV/m QP class A ( 10 m) at 30…230 MHz conforming to IEC 55011
Conducted emissions - test level: 79...63 dBμV/m QP ( power lines) at 150…1500 kHz conforming to IEC 55011
Radiated emissions - test level: 47 dBμV/m QP class A ( 10 m) at 230…1000 MHz conforming to IEC 55011
|
Immunity to microbreaks
|
10 ms
|
Ambient air temperature for operation
|
-10…50 °C (vertical installation)
-10…55 °C (horizontal installation)
|
Ambient air temperature for storage
|
-25…70 °C
|
Relative humidity
|
10…95 %, without condensation (in operation)
10…95 %, without condensation (in storage)
|
IP degree of protection
|
IP20 with protective cover in place
|
Pollution degree
|
2
|
Operating altitude
|
0...2000 m
|
Storage altitude
|
0…3000 m
|
Vibration resistance
|
3.5 mm at 5…8.4 Hz on symmetrical rail
3 gn at 8.4…150 Hz on symmetrical rail
3.5 mm at 5…8.4 Hz on panel mounting
3 gn at 8.4…150 Hz on panel mounting
|
Shock resistance
|
15 gn for 11 ms
|
SCIP Number
|
3d1fb974-648d-4978-8c59-b7dcc486f5a5
|
Packaging without single use plastic
|
Yes
|
Packaging made with recycled cardboard
|
Yes
|
REACh Regulation
|
REACh Declaration
|
EU RoHS Directive
|
Pro-active compliance (Product out of EU RoHS legal scope)
|
Mercury free
|
Yes
|
China RoHS Regulation
|
China RoHS declaration
|
RoHS exemption information
|
Yes
|
Environmental Disclosure
|
Product Environmental Profile
|
Circularity Profile
|
End of Life Information
|
WEEE
|
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
|
PVC free
|
Yes
|
California proposition 65
|
WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
|
Take-back
|
No
|
Carbon footprint (kg.eq.CO2 per CR, Total Life cycle)
|
2333
|