TM4ES4
network switch module, Modicon M241, 4 Ethernet switchs
|
|
|
Main
Product or component type
|
Ethernet unmanaged switch
|
Complementary
Range compatibility
|
Modicon M251
Modicon M241
|
Product compatibility
|
Modicon M241 logic controller
Modicon M251 logic controller
|
Current consumption
|
360 mA at 5 V DC for communication bus
|
Integrated connection type
|
Ethernet: 4 RJ45 connector
|
Transmission rate
|
10/100 Mbit/s
|
Port Ethernet
|
10BASE-T/100BASE-TX - 4 port(s) copper cable
|
Web services
|
Web server
|
Communication service
|
Modbus TCP server
Modbus TCP slave device
FTP
NGVL
Monitoring
IEC VAR ACCESS
Programming
SNMP
Modbus TCP client
Downloading
Updating firmware
Ethernet/IP slave device
DHCP client
|
Maximum number of connections
|
8 Modbus server
16 Ethernet/IP device
|
Communication port protocol
|
Ethernet IP/Modbus TCP
TCP (Transmission Control Protocol)
UDP (User Datagram Protocol)
SNMP
|
Redundancy
|
No
|
Local signalling
|
1 LED (green) for PWR
1 LED per channel (green/yellow) for Ethernet link
1 LED per channel (green) for Ethernet port activity
|
Electrical connection
|
RJ45 4 connectors for connecting Ethernet network
Screw connector terminal for connecting the functional ground
|
Marking
|
CE
|
Surge withstand
|
1 kV power lines (DC) common mode conforming to IEC 61000-4-5
2 kV power lines (AC) common mode conforming to IEC 61000-4-5
2 kV relay output common mode conforming to IEC 61000-4-5
1 kV I/O common mode conforming to IEC 61000-4-5
1 kV shielded cable common mode conforming to IEC 61000-4-5
0.5 kV power lines (DC) differential mode conforming to IEC 61000-4-5
1 kV power lines (AC) differential mode conforming to IEC 61000-4-5
1 kV relay output differential mode conforming to IEC 61000-4-5
0.5 kV I/O differential mode conforming to IEC 61000-4-5
|
Mounting support
|
Top hat type TH35-15 rail conforming to IEC 60715
Top hat type TH35-7.5 rail conforming to IEC 60715
Plate or panel with fixing kit
|
Width
|
25 mm
|
Height
|
90 mm
|
Depth
|
90 mm
|
Net weight
|
0.125 kg
|
Environment
Standards
|
UL 508
IEC 61131-2
|
Product certifications
|
cULus
C-Tick
|
Resistance to electrostatic discharge
|
8 kV in air conforming to IEC 61000-4-2
4 kV on contact conforming to IEC 61000-4-2
8 kV in air conforming to Marine specification (LR, ABS, DNV, GL)
6 kV on contact conforming to Marine specification (LR, ABS, DNV, GL)
|
Resistance to electromagnetic fields
|
10 V/m 80 MHz...1 GHz conforming to IEC 61000-4-3
3 V/m 1.4 GHz...2 GHz conforming to IEC 61000-4-3
1 V/m 2...2.7 GHz conforming to IEC 61000-4-3
|
Resistance to fast transients
|
2 kV (power lines) conforming to IEC 61000-4-4
2 kV (relay output) conforming to IEC 61000-4-4
1.5 kV (I/O) conforming to IEC 61000-4-4
1 kV (Ethernet line) conforming to IEC 61000-4-4
1 kV (serial link) conforming to IEC 61000-4-4
|
Resistance to conducted disturbances
|
10 V 0.15...80 MHz conforming to IEC 61000-4-6
3 V 0.1...80 MHz conforming to Marine specification (LR, ABS, DNV, GL)
10 V spot frequency (2, 3, 4, 6.2, 8.2, 12.6, 16.5, 18.8, 22, 25 MHz) conforming to Marine specification (LR, ABS, DNV, GL)
|
Electromagnetic emission
|
Conducted emissions - test level: 79 dBμV/m QP/66 dBμV/m AV ( power lines (AC)) at 0.15…0.5 MHz conforming to IEC 55011
Conducted emissions - test level: 73 dBμV/m QP/60 dBμV/m AV ( power lines (AC)) at 0.5…300 MHz conforming to IEC 55011
Conducted emissions - test level: 120...69 dBµV/m QP ( power lines) at 10…150 kHz conforming to IEC 55011
Conducted emissions - test level: 63 dBμV/m QP ( power lines) at 1.5…30 MHz conforming to IEC 55011
Radiated emissions - test level: 40 dBμV/m QP class A at 30…230 MHz conforming to IEC 55011
Radiated emissions - test level: 60...54 dBμV/m QP at 30…100 MHz conforming to Marine specification (LR, ABS, DNV, GL)
Radiated emissions - test level: 24 dBμV/m QP at 156…165 MHz conforming to Marine specification (LR, ABS, DNV, GL)
Conducted emissions - test level: 79...63 dBμV/m QP ( power lines) at 150…1500 kHz conforming to IEC 55011
Radiated emissions - test level: 47 dBμV/m QP class A at 230…1000 MHz conforming to IEC 55011
Radiated emissions - test level: 80...50 dμV/m QP at 150…30000 kHz conforming to Marine specification (LR, ABS, DNV, GL)
Radiated emissions - test level: 54 dBμV/m QP at 100…2000 MHz conforming to Marine specification (LR, ABS, DNV, GL)
|
Ambient air temperature for operation
|
-10…55 °C horizontal installation
-10…50 °C vertical installation
|
Ambient air temperature for storage
|
-25…70 °C
|
Relative humidity
|
10…95 %, without condensation (in operation)
10…95 %, without condensation (in storage)
|
IP degree of protection
|
IP20 with protective cover in place
|
Pollution degree
|
2
|
Operating altitude
|
0...2000 m
|
Storage altitude
|
0…3000 m
|
Vibration resistance
|
1 mm at 5…13.2 Hz on symmetrical rail
3 gn at 8.7…150 Hz on symmetrical rail
1 mm at 5…13.2 Hz on panel mounting
0.7 gn at 13.2…100 Hz on panel mounting
|
Shock resistance
|
15 gn for 11 ms
|
Packing Units
Unit Type of Package 1
|
PCE
|
Number of Units in Package 1
|
1
|
Package 1 Height
|
5.635 cm
|
Package 1 Width
|
11.532 cm
|
Package 1 Length
|
17.033 cm
|
Package 1 Weight
|
210.0 g
|
Unit Type of Package 2
|
S03
|
Number of Units in Package 2
|
20
|
Package 2 Height
|
30 cm
|
Package 2 Width
|
30 cm
|
Package 2 Length
|
40 cm
|
Package 2 Weight
|
5.04 kg
|
Unit Type of Package 3
|
P06
|
Number of Units in Package 3
|
160
|
Package 3 Height
|
75 cm
|
Package 3 Width
|
60 cm
|
Package 3 Length
|
80 cm
|
Package 3 Weight
|
48 kg
|
Offer Sustainability
Sustainable offer status
|
Green Premium product
|
REACh Regulation
|
REACh Declaration
|
EU RoHS Directive
|
Pro-active compliance (Product out of EU RoHS legal scope)
|
Mercury free
|
Yes
|
China RoHS Regulation
|
China RoHS declaration
|
RoHS exemption information
|
Yes
|
Environmental Disclosure
|
Product Environmental Profile
|
Circularity Profile
|
End of Life Information
|
WEEE
|
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
|
California proposition 65
|
WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
|
|
|