Schneider-Electric
 
TM4PDPS1 picture- web-product-data-sheet
TM4PDPS1
network switch module, Modicon M241, 1 Profibus DP slave
Schneider Electric
Characteristics
Main
Product or component type Profibus DP communication module
Complementary
Range compatibility Modicon M251
Modicon M241
Product compatibility Modicon M241 logic controller
Modicon M251 logic controller
Current consumption 290 mA at 5 V DC for communication bus
Power dissipation in W 1.5 W
Integrated connection type Profibus DP: female SUB-D 9 connector
Transmission rate 1.5 Mbit/s for bus length of 200 m
500 kbit/s for bus length of 400 m
187.5 kbit/s for bus length of 1000 m
9.6...93.75 kbit/s for bus length of 1200 m
3...12 Mbit/s for bus length of 100 m
Communication port protocol Profibus DP V0
Profibus DP V1
Insulation Between bus and internal logic at 1000 V DC
Local signalling 1 LED (green/yellow) for power supply
1 LED (green/red) for communication
Electrical connection Screw connector terminal for connecting the functional ground
SUB-D 9 1 female connector for connecting Profibus
Marking CE
Surge withstand 1 kV power lines (DC) common mode conforming to IEC 61000-4-5
2 kV power lines (AC) common mode conforming to IEC 61000-4-5
2 kV relay output common mode conforming to IEC 61000-4-5
1 kV I/O common mode conforming to IEC 61000-4-5
1 kV shielded cable common mode conforming to IEC 61000-4-5
0.5 kV power lines (DC) differential mode conforming to IEC 61000-4-5
1 kV power lines (AC) differential mode conforming to IEC 61000-4-5
1 kV relay output differential mode conforming to IEC 61000-4-5
0.5 kV I/O differential mode conforming to IEC 61000-4-5
Mounting support Top hat type TH35-15 rail conforming to IEC 60715
Top hat type TH35-7.5 rail conforming to IEC 60715
Plate or panel with fixing kit
Width 25 mm
Height 90 mm
Depth 90 mm
Net weight 0.1 kg
Environment
Standards IEC 61131-2
UL 508
EIA-485
Product certifications C-Tick
cULus
Resistance to electrostatic discharge 8 kV in air conforming to IEC 61000-4-2
4 kV on contact conforming to IEC 61000-4-2
8 kV in air conforming to Marine specification (LR, ABS, DNV, GL)
6 kV on contact conforming to Marine specification (LR, ABS, DNV, GL)
Resistance to electromagnetic fields 10 V/m 80 MHz...1 GHz conforming to IEC 61000-4-3
3 V/m 1.4 GHz...2 GHz conforming to IEC 61000-4-3
1 V/m 2...2.7 GHz conforming to IEC 61000-4-3
Resistance to fast transients 2 kV (power lines) conforming to IEC 61000-4-4
2 kV (relay output) conforming to IEC 61000-4-4
1.5 kV (I/O) conforming to IEC 61000-4-4
1 kV (Ethernet line) conforming to IEC 61000-4-4
1 kV (serial link) conforming to IEC 61000-4-4
Resistance to conducted disturbances 10 V 0.15...80 MHz conforming to IEC 61000-4-6
3 V 0.1...80 MHz conforming to Marine specification (LR, ABS, DNV, GL)
10 V spot frequency (2, 3, 4, 6.2, 8.2, 12.6, 16.5, 18.8, 22, 25 MHz) conforming to Marine specification (LR, ABS, DNV, GL)
Electromagnetic emission Conducted emissions - test level: 79 dBμV/m QP/66 dBμV/m AV ( power lines (AC)) at 0.15…0.5 MHz conforming to IEC 55011
Conducted emissions - test level: 73 dBμV/m QP/60 dBμV/m AV ( power lines (AC)) at 0.5…300 MHz conforming to IEC 55011
Conducted emissions - test level: 120...69 dBµV/m QP ( power lines) at 10…150 kHz conforming to IEC 55011
Conducted emissions - test level: 63 dBμV/m QP ( power lines) at 1.5…30 MHz conforming to IEC 55011
Radiated emissions - test level: 40 dBμV/m QP class A at 30…230 MHz conforming to IEC 55011
Radiated emissions - test level: 60...54 dBμV/m QP at 30…100 MHz conforming to Marine specification (LR, ABS, DNV, GL)
Radiated emissions - test level: 24 dBμV/m QP at 156…165 MHz conforming to Marine specification (LR, ABS, DNV, GL)
Conducted emissions - test level: 79...63 dBμV/m QP ( power lines) at 150…1500 kHz conforming to IEC 55011
Radiated emissions - test level: 47 dBμV/m QP class A at 230…1000 MHz conforming to IEC 55011
Radiated emissions - test level: 80...50 dμV/m QP at 150…30000 kHz conforming to Marine specification (LR, ABS, DNV, GL)
Radiated emissions - test level: 54 dBμV/m QP at 100…2000 MHz conforming to Marine specification (LR, ABS, DNV, GL)
Ambient air temperature for operation -10…55 °C horizontal installation
-10…50 °C vertical installation
Ambient air temperature for storage -25…70 °C
Relative humidity 10…95 %, without condensation (in operation)
10…95 %, without condensation (in storage)
IP degree of protection IP20 with protective cover in place
Pollution degree 2
Operating altitude 0...2000 m
Storage altitude 0…3000 m
Vibration resistance 1 mm at 5…13.2 Hz on symmetrical rail
3 gn at 8.7…150 Hz on symmetrical rail
1 mm at 5…13.2 Hz on panel mounting
0.7 gn at 13.2…100 Hz on panel mounting
Shock resistance 15 gn for 11 ms
Packing Units
Unit Type of Package 1 PCE
Number of Units in Package 1 1
Package 1 Height 17.0 cm
Package 1 Width 11.0 cm
Package 1 Length 5.4 cm
Package 1 Weight 210.0 g
Unit Type of Package 2 S03
Number of Units in Package 2 34
Package 2 Height 30 cm
Package 2 Width 30 cm
Package 2 Length 40 cm
Package 2 Weight 7.15 kg
Offer Sustainability
Sustainable offer status Green Premium product
REACh Regulation
print REACh Declaration
EU RoHS Directive Pro-active compliance (Product out of EU RoHS legal scope)
Mercury free Yes
China RoHS Regulation
print China RoHS declaration
RoHS exemption information
print Yes
Environmental Disclosure
print Product Environmental Profile
Circularity Profile
print End of Life Information
WEEE The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
California proposition 65 WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov