Standards
|
IEC 61131-2
UL 508
CSA C22.2 No 213
CSA C22.2 No 142
|
Product certifications
|
CSA
GOST-R
cULus
C-Tick
|
Ambient air temperature for operation
|
-10…55 °C without derating (horizontal installation)
55…60 °C with derating factor (horizontal installation)
-10…50 °C (vertical installation)
|
Ambient air temperature for storage
|
-25…70 °C
|
Relative humidity
|
5…95 % without condensation
|
Operating altitude
|
0...2000 m
|
Storage altitude
|
0…3000 m
|
Vibration resistance
|
1 gn at 8.4…150 Hz on DIN rail
3.5 mm at 5…8.4 Hz on DIN rail
|
Shock resistance
|
15 gn for 11 ms
|
Resistance to electrostatic discharge
|
4 kV on contact conforming to EN/IEC 61000-4-2
8 kV in air conforming to EN/IEC 61000-4-2
|
Resistance to electromagnetic fields
|
1 V/m 2...2.7 GHz conforming to EN/IEC 61000-4-3
10 V/m 80...2000 MHz conforming to EN/IEC 61000-4-3
|
Resistance to fast transients
|
1 kV (I/O) conforming to EN/IEC 61000-4-4
1 kV (shielded cable) conforming to EN/IEC 61000-4-4
2 kV (power lines) conforming to EN/IEC 61000-4-4
|
Surge withstand
|
0.5 kV differential mode conforming to EN/IEC 61000-4-5
1 kV common mode conforming to EN/IEC 61000-4-5
|
Electromagnetic compatibility
|
EN/IEC 61000-4-6
|
Disturbance radiated/conducted
|
CISPR 11
|