Analogue input type
|
Thermocouple - 200...1000 °C with thermocouple J
Thermocouple - 200...1300 °C with thermocouple K
Thermocouple 0...1760 °C with thermocouple R
Thermocouple 0...1760 °C with thermocouple S
Thermocouple 0...1820 °C with thermocouple B
Thermocouple - 200...400 °C with thermocouple T
Thermocouple - 200...1300 °C with thermocouple N
Thermocouple - 200...800 °C with thermocouple E
Thermocouple 0...2315 °C with thermocouple C
Ni 100/Ni 1000 temperature probe - 60...180 °C
Pt 100 temperature probe - 200...850 °C
Pt 1000 temperature probe - 200...600 °C
|
Analogue input resolution
|
14 bits
|
LSB value
|
0.1 °C
|
Sampling duration
|
125 ms, analogue input type: thermocouple
250 ms, analogue input type: temperature probe
|
Absolute accuracy error
|
+/- 0.1 % of full scale at 25 °C for Pt 100/Pt 1000, Ni 100/ Ni 1000 temperature probe
+/- 0.4 % of full scale at 25 °C for thermocouple K - 200...0 °C
+/- 0.1 % of full scale at 25 °C for thermocouple K 0...1300 °C
+/- 0.4 % of full scale at 25 °C for thermocouple J - 200...0 °C
+/- 0.1 % of full scale at 25 °C for thermocouple J 0...1000 °C
+/- 0.4 % of full scale at 25 °C for thermocouple E - 200...0 °C
+/- 0.1 % of full scale at 25 °C for thermocouple E 0...800 °C
+/- 0.4 % of full scale at 25 °C for thermocouple T - 200...0 °C
+/- 0.1 % of full scale at 25 °C for thermocouple T 0...400 °C
+/- 0.4 % of full scale at 25 °C for thermocouple N - 200...0 °C
+/- 0.1 % of full scale at 25 °C for thermocouple N 0...1300 °C
+/- 6 °C at 25 °C for thermocouple R, S 0...200 °C
+/- 0.1 % of full scale at 25 °C for thermocouple R, S 200...1760 °C
+/- 0.1 % of full scale at 25 °C for thermocouple C 0...2315 °C
|
Temperature drift
|
+/- 0.02 %FS/°C
|
Repeat accuracy
|
+/- 0.5 %FS
|
Non-linearity
|
+/- 0.01 %FS
|
Cross talk
|
<= 1 LSB
|
Type of cable
|
Twisted shielded pairs cable
|
Electrical connection
|
3 x 1.5 mm² 2 screw terminal blocks with pitch 3.81 mm adjustment for inputs
|
Maximum cable distance between devices
|
Twisted shielded pairs cable: <30 m for input
|
Insulation
|
Non-insulated between analogue input and internal logic
|
Height
|
41 mm
|
Depth
|
15 mm
|
Width
|
35 mm
|
Net weight
|
0.015 kg
|
Input impedance
|
>= 1 MOhm
|