Characteristics
Main
Range of product Modicon M221
Product or component type Graphic display
Range compatibility Modicon M221
Current consumption 40 mA at 5 V DC via RJ45 connector
Power consumption in W 1 W
Display type Backlit colour STN LCD
Display colour Monochrome
Display resolution 240 x 160 pixels
Number of key 4 configurable
6 for navigation
Complementary
Standards IEC 61131-2
IEC 61010-2-201
Product certifications cULus
Marking CE
Mounting location Front cabinet diameter: 22 mm hole
Bottom of cabinet diameter: 22 mm hole, connection via mounting accessory
Connector type RJ45 for communication and power supply
Height 126 mm
Width 80 mm
Depth 63 mm
Net weight 0.17 kg
Environment
Ambient air temperature for operation -15…50 °C
Operating altitude 0...2000 m
Storage altitude 0…2000 m
Environmental characteristic Corrosive gas free
Relative humidity 95 %, non-condensing (transport)
95 %, non-condensing (storage)
95 %, non-condensing (operation)
Ambient air temperature for storage -40…70 °C
IP degree of protection IP65 front face:
IP20 back part:
Pollution degree 2 conforming to IEC 60664-1
Vibration resistance 1.5 mm (f= 3…150 Hz)
2 gn
Shock resistance 15 gn for 11 ms
Electromagnetic compatibility Electrostatic discharge - test level: 8 kV (air discharge) conforming to IEC 61000-4-2
Electrostatic discharge - test level: 4 kV (contact discharge) conforming to IEC 61000-4-2
Radiated radio-frequency electromagnetic field immunity test - test level: 10 V/m (80 MHz...1 GHz) conforming to IEC 61000-4-3
Radiated radio-frequency electromagnetic field immunity test - test level: 3 V/m (1.4...2 GHz) conforming to IEC 61000-4-3
Radiated radio-frequency electromagnetic field immunity test - test level: 1 V/m (2...3 GHz) conforming to IEC 61000-4-3
Magnetic field at power frequency - test level: 30 A/m (50/60 Hz) conforming to IEC 61000-4-8
Electrical fast transient/burst immunity test - test level: 1 kV conforming to IEC 61000-4-4
Surge immunity test - test level: 0.5 kV (common mode) conforming to IEC 61000-4-5
Surge immunity test - test level: 0.5 kV (differential mode) conforming to IEC 61000-4-5
Conducted RF disturbances - test level: 10 Vrms (0.15...80 MHz) conforming to IEC 61000-4-6
Disturbing field emission - test level: 10...150 kHz (power lines (DC)) conforming to IEC 55011
Disturbing field emission - test level: 120...69 dBµV/m QP (power lines (DC)) conforming to IEC 55011
Disturbing field emission - test level: 150...1500 kHz (power lines (DC)) conforming to IEC 55011
Disturbing field emission - test level: 1.5...30 kHz (power lines (DC)) conforming to IEC 55011
Disturbing field emission - test level: 30...230 MHz class A (10 m) conforming to IEC 55011
Disturbing field emission - test level: 230 MHz...1 GHZ class A (10 m) conforming to IEC 55011
Disturbing field emission - test level: 79...63 dBμV/m QP (power lines (DC)) conforming to IEC 55011
Disturbing field emission - test level: 63 dBμV/m QP (power lines (DC)) conforming to IEC 55011
Disturbing field emission - test level: 40 dBμV/m QP class A (10 m) conforming to IEC 55011
Disturbing field emission - test level: 47 dBμV/m QP class A (10 m) conforming to IEC 55011
Packing Units
Unit Type of Package 1 PCE
Number of Units in Package 1 1
Package 1 Height 6.3 cm
Package 1 Width 8.0 cm
Package 1 Length 12.6 cm
Package 1 Weight 164.0 g
Unit Type of Package 2 S03
Number of Units in Package 2 12
Package 2 Height 30.0 cm
Package 2 Width 30.0 cm
Package 2 Length 40.0 cm
Package 2 Weight 4.375 kg
Unit Type of Package 3 P06
Number of Units in Package 3 96
Package 3 Height 70.0 cm
Package 3 Width 60.0 cm
Package 3 Length 80.0 cm
Package 3 Weight 15.744 kg
Offer Sustainability
Sustainable offer status Green Premium product
REACh Regulation
print REACh Declaration
EU RoHS Directive Pro-active compliance (Product out of EU RoHS legal scope)
Mercury free Yes
RoHS exemption information
print Yes
China RoHS Regulation
print China RoHS declaration
Environmental Disclosure
print Product Environmental Profile
Circularity Profile
print End of Life Information
California proposition 65 WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov