Line current
|
177 A at 400 V
160 A at 480 V
|
Input power
|
123 kW at 400 V
133 kW at 480 V
|
Continuous output current
|
185 A at 400 V
163 A at 480 V
|
Output voltage
|
650 V DC - supply: 380...400 V AC
720 V DC - supply: 440 V AC
770 V DC - supply: 480 V AC
|
Thermal losses
|
2250 W
|
Max current
|
1.20 x nominal current (duration = 60 s)
1.35 x nominal current (duration = 2 s)
|
Maximum voltage drop at rated load
|
<30 % at 380...400 V, <= 60 s
<40 % at 440 V, <= 60 s
<40 % at 480 V, <= 60 s
|
Communication port protocol
|
CANopen
Modbus
|
Connector type
|
1 RJ45 for Modbus
Male SUB-D 9 on RJ45 for CANopen
|
Option card
|
Communication bridge
|
Operating position
|
Vertical +/- 10 degree
|
Height
|
680 mm
|
Width
|
310 mm
|
Depth
|
377 mm
|
Product weight
|
60 kg
|
Environmental characteristic
|
3K3 conforming to EN/IEC 60721-3-3
3C2 conforming to EN 60721-3-3
3S2 conforming to EN 60721-3-3
|
Relative humidity
|
0…95 %
|
Ambient air temperature for operation
|
45…60 °C (with current derating of 2 % per °C)
-10…45 °C
|
Ambient air temperature for storage
|
-25…70 °C
|
Operating altitude
|
<= 1000 m without derating
1000...3000 m with current derating 1 % per 100 m
|
Pollution degree
|
2 conforming to EN 61800-5-1
|
Vibration resistance
|
1.5 mm (f= 3…10 Hz) conforming to EN/IEC 60068-2-6
0.6 gn (f= 10…200 Hz) conforming to EN/IEC 60068-2-6
|
Shock resistance
|
7 gn for 11 ms conforming to EN/IEC 60721-3-3
|
Air flow surface
|
500 cm²
|
Volume of cooling air
|
400 m3/h for power circuit
115 m3/h for control circuit
|
IP degree of protection
|
IP00
|
Standards
|
EN/IEC 61800-5-1
|
Product certifications
|
CE
UL (pending)
CSA (pending)
|