Range of product
|
Preventa Safety automation
|
Product or component type
|
Configurable safety controller
|
Safety module name
|
XPSMC
|
Safety use category
|
Category 4 maximum conforming to EN 954-1/EN/ISO 13849-1
PLE maximum conforming to ISO 13849-1
SIL 3 maximum conforming to IEC 61508
|
Type of start
|
Configurable
|
Standards
|
EN 1760-1/ISO 13856-1
EN 574/ISO 13851
IEC 60947-5-1
IEC 61508
IEC 60204-1
EN 954-1/EN/ISO 13849-1
IEC 61496-1
|
Product certifications
|
UL
CSA
TÜV
|
[Us] rated supply voltage
|
24 V DC - 20...20 %
|
Number of inputs
|
16
|
Communication port protocol
|
Modbus with 1 RJ45 port(s), serial link, transmission rate: 1200 bps, 2400 bps, 4800 bps, 9600 bps or 19200 bps
Profibus with 1 SUB-D 9-pin female port(s), serial link, transmission rate: 12 Mbps
|
Safety level
|
Can reach PL e/category 4 conforming to EN 954-1/EN/ISO 13849-1
Can reach SIL 3 conforming to IEC 61508
|
Function of module
|
Dynamic monitoring of hydraulic valves on linear presses
Eccentric press
Emergency stop monitoring, with or without time delay, 1 or 2-channel wiring
Enabling switch monitoring, 2 or 3 contacts
Foot switch monitoring
Guard monitoring for injection presses and blowing machines
Guard monitoring with 1 or 2 limit switches
Hydraulic press
Magnetic switch monitoring category 4 conforming to EN/IEC 61496
Monitoring safety stop at top dead centre on eccentric press category 3 conforming to EN 574/ISO 13851
Muting function of light curtains
Position selector
Safety mat monitoring
Safety time delays
Shaft/chain breaking monitor
Zero speed detection
Light curtain monitoring category 4 conforming to IEC 61496
Two-hand control category 3 conforming to EN 574/ISO 13851
|
Synchronisation time between inputs
|
Depending on configuration selected
|
Power consumption in W
|
12 W
|
Input protection type
|
External fuse 16 A
|
[Uc] control circuit voltage
|
28.8 V
|
Maximum line resistance
|
100 Ohm <2000 m
|
Output type
|
2 relays, 2 NO contacts (4 NO total) circuit(s)
Solid state, 6 circuit(s), volt-free
|
Breaking capacity
|
180 VA holding AC-15 C300 relay output
1800 VA inrush AC-15 C300 relay output
|
Breaking capacity
|
2 A at 24 V for static output circuit
1.5 A at 24 V (DC-13) time constant: 50 ms for relay output
|
Output thermal current
|
4 A for both outputs simultaneously
6 A for 1 output and 2 A for the other for relay output
|
[Ith] conventional free air thermal current
|
16 A for relay output
6.5 A for static output circuit
|
Associated fuse rating
|
16 A gL for power supply
4 A gL for relay output
6 A fast blow for relay output
|
Minimum output current
|
10 mA for relay output
|
Minimum output voltage
|
17 V for relay output
|
Response time
|
Configurable : 20 ms or 30 ms with software XPSMCWIN
|
[Ui] rated insulation voltage
|
300 V (pollution degree 2) conforming to IEC 60647-5-1, DIN VDE 0110 part 1
|
[Uimp] rated impulse withstand voltage
|
4 kV overvoltage category III conforming to IEC 60647-5-1, DIN VDE 0110 part 1
|
Method of access
|
Slave
|
Exchange size
|
14 words
|
Number of addresses
|
1…125 for Profibus
1…247 for Modbus
|
Parity
|
Even for Modbus
No for Modbus
Odd for Modbus
|
Data format
|
1 start bit/8 data bits
1 stop bit even or odd
2 stop bits without parity
RTU (Remote Terminal Unit) mode
|
Supported modbus function
|
01: 8-bit output data/32-bit input data
02: 32-bit input data/8-bit output data
03: information and errors
|
Local signalling
|
32 LEDs
|
Mounting support
|
Mounting plate
|
Depth
|
153 mm
|
Height
|
151.5 mm
|
Width
|
74 mm
|
Net weight
|
0.82 kg
|