Power dissipation in W
|
3 W
|
Quality labels
|
CE
|
Range compatibility
|
Preventa XPSMCM
|
Connector type
|
Male SUB-D 9
|
Number of port
|
1
|
Method of access
|
Server
|
Transmission rate
|
10 kbit/s
20 kbit/s
50 kbit/s
100 kbit/s
125 kbit/s
250 kbit/s
500 kbit/s
800 kbit/s
1 Mbit/s
Autodetected
|
Communication port protocol
|
CANopen
|
Current consumption
|
0.125 mA
|
Maximum cable distance between devices
|
2500 m
1000 m
750 m
500 m
250 m
100 m
50 m
25 m
|
Local signalling
|
LED green with PWR marking for power ON
LED green with RUN marking for operating
LED red with E IN marking for internal error
LED red with E EX marking for external error
LED green/red with OP marking for operating
LED green/red with ERR marking for communication error
|
Connections - terminals
|
2 spring clamp terminals, removable terminal block
|
Cable cross section
|
0.2…2.5 mm² - AWG 24...AWG 14 flexible cablewithout cable end
0.25…2.5 mm² - AWG 23...AWG 14 flexible cablewith cable end, with bezel
0.25…2.5 mm² - AWG 23...AWG 14 flexible cablewith cable end, without bezel
0.2…2.5 mm² - AWG 24...AWG 14 solid cablewithout cable end
0.5…1 mm² - AWG 20...AWG 18 flexible cablewith cable end, with double bezel
|
Mounting support
|
Omega 35 mm DIN rail conforming to EN 50022
|
Width
|
22.5 mm
|
Height
|
99 mm
|
Depth
|
114.5 mm
|
Net weight
|
0.3 kg
|
Product certifications
|
cULus
RCM
TÜV
|
IP degree of protection
|
IP20
|
Ambient air temperature for operation
|
-10…55 °C
|
Ambient air temperature for storage
|
-20…85 °C
|
Relative humidity
|
10…95 %
|
Pollution degree
|
2
|
Insulation
|
250 V AC between power supply and housing conforming to EN/IEC 61800-5-1
|
Overvoltage category
|
II
|
Electromagnetic compatibility
|
Electrostatic discharge immunity test - test level: 6 kV (on contact) conforming to EN/IEC 61000-4-2
Electrostatic discharge immunity test - test level: 20 kV (on air) conforming to EN/IEC 61000-4-2
Susceptibility to electromagnetic fields - test level: 10 V/m (80...1000 MHz) conforming to EN/IEC 61000-4-3
Susceptibility to electromagnetic fields - test level: 30 V/m (1.4 GHz...2 GHz) conforming to EN/IEC 61000-4-3
|
Vibration resistance
|
+/-0.35 mm (f= 10…55 Hz) conforming to EN/IEC 61496-1
|
Shock resistance
|
10 gn (duration = 16 ms) for 1000 shocks on each axis conforming to EN/IEC 61496-1
|
Operating altitude
|
2000 m
|
Service life
|
20 year(s)
|