Power consumption in W
|
3 W
|
Power dissipation in W
|
3 W
|
Integrated connection type
|
Backplane expansion bus
|
Number of terminal blocks
|
6
|
Connections - terminals
|
1 spring clamp terminals, removable terminal block
2 spring clamp terminals, removable terminal block
|
Load type
|
Resistive load
|
Group of channels
|
4 dual channel for load 400mA/output
|
Safety level
|
Can reach category 4 conforming to ISO 13849-1
Can reach PL = e conforming to ISO 13849-1
Can reach SIL 3 conforming to IEC 61508
SILCL 3 conforming to IEC 62061
|
Quality labels
|
CE
|
Discrete input voltage
|
24 V DC
|
Discrete output voltage
|
24 V DC
|
Discrete output current
|
400 mA
100 mA
|
Output load
|
60 Ohm
|
Local signalling
|
1 LED green with PWR marking for power ON
1 LED green with RUN marking for RUN (status)
1 LED red with E IN marking for internal error
1 LED red with E EX marking for external error
2 LEDs orange with ADDR marking for node address
4 LEDs green/red with OUT marking for output status
4 LEDs yellow with RST marking for restart signal
4 LEDs yellow with STATUS marking for output status
|
Cable cross section
|
0.2…2.5 mm² - AWG 24...AWG 14 flexible cablewithout cable end
0.25…2.5 mm² - AWG 23...AWG 14 flexible cablewith cable end, with bezel
0.25…2.5 mm² - AWG 23...AWG 14 flexible cablewith cable end, without bezel
0.2…2.5 mm² - AWG 24...AWG 14 solid cablewithout cable end
0.5…1 mm² - AWG 20...AWG 18 flexible cablewith cable end, with double bezel
|
Mounting support
|
Omega 35 mm DIN rail conforming to EN 50022
|
Depth
|
22.5 mm
|
Height
|
99 mm
|
Width
|
114.5 mm
|
Net weight
|
0.25 kg
|
Standards
|
IEC 61508
IEC 61800-5-1
ISO 13849-1
IEC 62061
|
Product certifications
|
RCM
cULus
TÜV
|
IP degree of protection
|
IP20 (enclosure)
|
Ambient air temperature for operation
|
-10…55 °C
|
Ambient air temperature for storage
|
-20…85 °C
|
Relative humidity
|
10…95 %
|
Pollution degree
|
2
|
[Uimp] rated impulse withstand voltage
|
4 kV conforming to IEC 61800-5-1
|
Safety reliability data
|
DC > 99 %
MTTFd < 100 years high
PFHd = 3.44E-9 1/h
|
Insulation
|
250 V AC between power supply and housing conforming to IEC 61800-5-1
|
Overvoltage category
|
II
|
Electromagnetic compatibility
|
Electrostatic discharge immunity test - test level: 6 kV (on contact) conforming to IEC 61000-4-2
Electrostatic discharge immunity test - test level: 20 kV (on air) conforming to IEC 61000-4-2
Susceptibility to electromagnetic fields - test level: 10 V/m (80...1000 MHz) conforming to IEC 61000-4-3
Susceptibility to electromagnetic fields - test level: 30 V/m (1.4 GHz...2 GHz) conforming to IEC 61000-4-3
|
Vibration resistance
|
+/-0.35 mm (f= 10…55 Hz) conforming to IEC 61496-1
|
Shock resistance
|
10 gn (duration = 16 ms) for 1000 shocks on each axis conforming to IEC 61496-1
|
Service life
|
20 year(s)
|