Maximum power dissipation in W
|
3 W
|
Integrated connection type
|
Not connected to backplane expansion bus
|
Switching voltage
|
10 V DC
|
Associated fuse rating
|
3.5 A, slow-blow
|
Safety level
|
Can reach category 4 conforming to ISO 13849-1
Can reach PL = e conforming to ISO 13849-1
Can reach SIL 3 conforming to IEC 61508
SILCL 3 conforming to IEC 62061
|
Quality labels
|
CE
|
Output type
|
Relay, 2 NO + 1 NC circuit(s), volt-free
|
Quantity per set
|
1
|
Switching time
|
12 ms
|
Maximum switching voltage
|
400 V AC
250 V DC
|
Minimum switching current
|
20 mA
|
Maximum switching current
|
6 A
|
Number of terminal blocks
|
4
|
Local signalling
|
1 LED green with PWR marking for power ON
1 LED green with RUN marking for RUN (status)
1 LED red with E IN marking for internal error
1 LED red with E EX marking for external error
2 LEDs orange with ADDR marking for node address
1 LED green/red with RELAY K1 marking for relay contact
|
Connections - terminals
|
1 spring clamp terminals, removable terminal block
2 spring clamp terminals, removable terminal block
|
Cable cross section
|
0.2…2.5 mm² - AWG 24...AWG 14 flexible cablewithout cable end
0.25…2.5 mm² - AWG 23...AWG 14 flexible cablewith cable end, with bezel
0.25…2.5 mm² - AWG 23...AWG 14 flexible cablewith cable end, without bezel
0.2…2.5 mm² - AWG 24...AWG 14 solid cablewithout cable end
0.5…1 mm² - AWG 20...AWG 18 flexible cablewith cable end, with double bezel
|
Mounting support
|
Omega 35 mm DIN rail conforming to EN 50022
|
Width
|
22.5 mm
|
Height
|
99 mm
|
Depth
|
114.5 mm
|
Net weight
|
0.25 kg
|
Standards
|
IEC 62061
ISO 13849-1
IEC 61800-5-1
IEC 61508
|
Product certifications
|
RCM
TÜV
cULus
|
IP degree of protection
|
IP20
|
Ambient air temperature for operation
|
-10…55 °C
|
Ambient air temperature for storage
|
-20…85 °C
|
Relative humidity
|
10…95 %
|
Pollution degree
|
2
|
[Uimp] rated impulse withstand voltage
|
4 kV conforming to IEC 61800-5-1
|
Safety reliability data
|
B10d = 300000 utilisation category AC-15 230 V, , <3 A conforming to ISO 13849-1
B10d = 750000 utilisation category AC-15 230 V, , <1 A conforming to ISO 13849-1
B10d = 10000000 utilisation category DC-13 24 V, , <2 A conforming to ISO 13849-1
|
Insulation
|
250 V AC between power supply and housing conforming to IEC 61800-5-1
|
Overvoltage category
|
II
|
Electromagnetic compatibility
|
Electrostatic discharge immunity test - test level: 6 kV (on contact) conforming to IEC 61000-4-2
Electrostatic discharge immunity test - test level: 20 kV (on air) conforming to IEC 61000-4-2
Susceptibility to electromagnetic fields - test level: 10 V/m (80...1000 MHz) conforming to IEC 61000-4-3
Susceptibility to electromagnetic fields - test level: 30 V/m (1.4 GHz...2 GHz) conforming to IEC 61000-4-3
|
Vibration resistance
|
+/-0.35 mm (f= 10…55 Hz) conforming to IEC 61496-1
|
Shock resistance
|
10 gn for 16 ms (1000 shocks on each axis) conforming to IEC 61496-1
|
Electrical durability
|
20000000 cycles
|
Mechanical durability
|
20000000 cycles
|
Service life
|
20 year(s)
|