Range compatibility
|
AS-Interface cabling system
|
Material
|
Glass reinforced polyamide: base unit
Polycarbonate: cover unit
|
Mounting diameter
|
70 mm
|
[Us] rated supply voltage
|
External: 19.2...30 V
AS-Interface line: 24...31.6 V
|
Current consumption
|
250 mA under load via AS-Interface line
30 mA under load external
30 mA no load
|
Actuator sensor interface profile [AS-i]
|
S.7.F
|
Electrical connection
|
1 remote connector M12, cable length: 1 m for AS-Interface line
|
Cable entry
|
Side entry
|
Assembly style
|
Customer assembly, up to 5 units
|
[Ui] rated insulation voltage
|
250 V conforming to IEC 60947-1
|
[Uimp] rated impulse withstand voltage
|
4 kV conforming to IEC 60947-1
|
Terminals description ISO n°1
|
(COM-4)PW
(COM-2)PW
(COM-3)PW
(COM-1)PW
(GND)GROUND
(COM-5)PW
|
Net weight
|
0.3 kg
|
Product certifications
|
CSA
EAC
AS-Interface No 25701
|
Standards
|
EN/IEC 60947-5-1
|
Protective treatment
|
TC
|
Ambient air temperature for storage
|
-20…70 °C
|
Ambient air temperature for operation
|
-10…50 °C
|
Shock resistance
|
25 gn conforming to IEC 60068-2-27
|
Vibration resistance
|
5 gn conforming to IEC 60068-2-6
|
Overvoltage category
|
Class I conforming to IEC 60536
|
IP degree of protection
|
IP65 conforming to IEC 60529
|
NEMA degree of protection
|
Type 4X conforming to UL (indoor)
|