Maximum radio communication distance
|
100 m in free field
250 m if a relay antenna is located between the transmitter and Harmony Hub
60 m if an external antenna is connected to Harmony Hub
25 m with Harmony Hub installed in a metal housing or in a closed metal enclosure
|
Radio response time
|
< 30 ms
|
Radio channels utilisation
|
<= 60 devices
|
[Us] rated supply voltage
|
24...240 V AC/DC 50/60 Hz - 10...10 %
|
Immunity to microbreaks
|
10 ms
|
Maximum power consumption in W
|
4 W AC/DC
|
Breaking capacity
|
15 W
|
Breaking capacity
|
750 VA
|
Control circuit frequency
|
50...60 Hz +/- 10 %
|
Short-circuit protection
|
16 A GB2 circuit breaker
|
Operating position
|
Any position
|
Mounting support
|
35 mm symmetrical DIN rail conforming to EN/IEC 60715
Mounting plate
|
Electrical connection
|
1 conductor cable 0.2…4 mm² - AWG 24...AWG 12 - solid - without cable end conforming to IEC 60947-1
2 conductors cable 0.2…1.5 mm² - AWG 24...AWG 16 - solid - without cable end conforming to IEC 60947-1
1 conductor cable 0.2…0.75 mm² - AWG 24...AWG 14 - flexible - with cable end conforming to IEC 60947-1
2 conductors cable 0.2…2.5 mm² - AWG 24...AWG 18 - flexible - with cable end conforming to IEC 60947-1
|
Tightening torque
|
0.35…0.4 N.m conforming to EN/IEC 60947-1
0.35…0.40 N.m conforming to EN/IEC 60947-1
|
Housing material
|
Self-extinguishing plastic
|
Status LED
|
1 LED green for power ON
1 LED yellow for communication network
5 LEDs red for function mode
1 LED green and yellow for reception signal
|
Rated short-duration power frequency withstand voltage
|
1.5 kV 50 Hz conforming to EN/IEC 60947-5-1
|
[Uimp] rated impulse withstand voltage
|
4 kV
|
Surge withstand
|
1 kV differential mode conforming to IEC 61000-4-5
2 kV common mode conforming to IEC 61000-4-5
|
Width
|
122 mm
|
Height
|
90 mm
|
Depth
|
60 mm
|
Net weight
|
0.27 kg
|
Antenna gain
|
0 dBi
|
Integrated connection type
|
1 isolated serial link 2 x RJ45 in parallel Modbus Serial line slave Modbus slave RTU asynchronous in baseband RS485, half duplex, 1.2...115.2 kbauds, 2 twisted shielded pairs
|
Data storage equipment
|
SD card
|
Topology
|
Devices linked by daisy-chaining or tap junctions
|
Data format
|
7 or 8 bits, 1 or 2 stop bits
|
Parity
|
No
Even
Odd
|
Radio agreement
|
ANATEL, type III conforming to ETSI EN 301 489-3
FCC, category 2 conforming to ETSI EN 300 440-1
ICASA
RSS, category 1 conforming to ETSI EN 300 440-1
SRRC
|
Product certifications
|
GOST
CE
UL
C-Tick
CSA
CCC
|
Directives
|
2006/95/EC - low voltage directive
2004/108/EC - electromagnetic compatibility
1999/5/EC - R&TTE directive
|
Standards
|
CSA C22.2 No 14
EN 62311
EN/IEC 61131-2
ETSI EN 300 440-2
ETSI EN 300 328
EN/IEC 60950-1
UL 508
|
Ambient air temperature for storage
|
-40…70 °C
|
Relative humidity
|
90 % at -25…55 °C, without condensation conforming to ETSI EN 300 440-1
|
Operating altitude
|
0...2000 m
|
Storage altitude
|
0…3000 m
|
Vibration resistance
|
+/- 3.5 mm (f = 5…14 Hz) conforming to IEC 60068-2-6
1 gn (f = 5…150 Hz) on panel mounting conforming to IEC 60068-2-6
2 gn (f = 8…150 Hz) on DIN rail conforming to IEC 60068-2-6
|
Shock resistance
|
10 gn (duration = 16 ms) for 6000 shocks conforming to IEC 60068-2-27
|
IP degree of protection
|
IP20 (casing) conforming to IEC 60529
IP20 (terminals)
|
Pollution degree
|
2 conforming to IEC 60664-1
|
Electromagnetic compatibility
|
1.2/50 µs shock waves immunity test - test level: 1 kV (differential mode) conforming to IEC 61000-4-5
1.2/50 µs shock waves immunity test - test level: 2 kV (common mode) conforming to IEC 61000-4-5
Immunity to microbreaks and voltage drops - test level: 10 ms conforming to IEC 61000-4-11
|
Dielectric strength
|
3000 V between input and output AC
4250 V between input and output DC
1500 V between input and ground AC
2150 V between input and ground DC
|