Schneider-Electric
 
ZBRTT1 picture- web-product-data-sheet
ZBRTT1
Wireless transmitter, Harmony XB5R, Transmitter components for wireless temperature sensors, green, 2400MHz
Schneider Electric
Characteristics
Main
Range of product Harmony XB5R
Product or component type Wireless transmitter
Device short name XB5R
Transmission frequency 2400 MHz
Antenna type Omnidirectional
Complementary
Max power consumption in W 60 mW
Number of channels 16
Modulation Technique O-QPSK
Bandwidth 5 MHz
Antenna gain 0 dBi
CAD overall height 21 mm
CAD overall width 40 mm
CAD overall depth 40 mm
Product weight 0.034 kg
Measurement temperature 90 °C
Mechanical robustness Free fall resistance 1000 mm conforming to IEC 60068-2-32
Standards IEC 61010-1
UL 61010-1
IEEE 802.15.4
Radio agreement ANATEL
ARIB T66
FCC
ICASA
RSS
SRRC
Communication port protocol Zigbee green power at 2.4 GHz conforming to IEEE 802.15.4
Maximum sensing distance 100 m in free field
25 m transmitter in a plastic box type XAL D and receiver in a metal enclosure
10 m transmitter in box type XAL D, receiver in metal enclosure and use relay-antenna
Acquisition time 2 ms
Response time < 2 ms
Fixing mode Magnetic fixing
Mounting mode Magnetic
Electrical composition code PW1
Environment
Ambient air temperature for storage -40…70 °C
Ambient air temperature for operation -40…70 °C
Relative humidity 10…95 % at -40…70 °C
IP degree of protection IP54 conforming to IEC 60529
IK degree of protection IK06 conforming to IEC 62262
Shock resistance 40 gn (duration = 6 ms) for 3 shocks conforming to IEC 60068-2-27
20 gn (duration = 16 ms) for 1000 shocks conforming to IEC 60068-2-27
10 gn (duration = 11 ms) for 3 shocks conforming to IEC 60068-2-27
Vibration resistance 2 gn (f= 5…200 Hz) conforming to IEC 60068-2-6
4 gn (f= 200…500 Hz) conforming to IEC 60068-2-6
1 gn (f= 10…2000 Hz) conforming to IEC 60068-2-64
1 gn (f= 5…500 Hz) conforming to IEC 60068-2-6
Electromagnetic compatibility Susceptibility to electromagnetic fields - test level: 25 V/m (80 MHz...6 GHz) conforming to IEC 61000-4-3
Susceptibility to conducted disturbances - test level: 20 V (0.15...80 MHz) conforming to IEC 61000-4-6
Electromagnetic field immunity test - test level: 1000 A/m (pulsed) conforming to IEC 61000-4-8
Electromagnetic field immunity test - test level: 300 A/m (continuous) conforming to IEC 61000-4-8
Electromagnetic field immunity test - test level: 1000 A/m (pulsed) conforming to EN/IEC 61000-4-9
Damped oscillatory wave - test level: 3 kV conforming to IEC 61000-4-10
Damped oscillatory wave - test level: 2.5 kV conforming to EN/IEC 61000-4-18
Surge immunity test conforming to EN/IEC 61000-4-18
Surge immunity test (common mode) conforming to IEC 61000-4-5
Immunity to conducted RF disturbances - test level: 30 V (differential mode) conforming to IEC 61000-4-5
Immunity to conducted RF disturbances (continuous) conforming to IEC 61000-4-16
Immunity to conducted RF disturbances - test level: 300 V
Immunity to conducted RF disturbances (short term) conforming to IEC 61000-4-16
Product certifications CSA
CCC
UL
GOST
C-Tick
BT 2006/95/EC
Directives 2004/108/EC - electromagnetic compatibility
1999/5/EC - R&TTE directive
Packing Units
Unit Type of Package 1 PCE
Number of Units in Package 1 1
Package 1 Height 4.5 cm
Package 1 Width 4.5 cm
Package 1 Length 9.0 cm
Package 1 Weight 62.0 g
Unit Type of Package 2 S03
Number of Units in Package 2 100
Package 2 Height 30.0 cm
Package 2 Width 30.0 cm
Package 2 Length 40.0 cm
Package 2 Weight 6.569 kg
Offer Sustainability
Packaging without single use plastic No
Packaging made with recycled cardboard No
SCIP Number 25b7f895-3732-43c8-9910-ef6005058640
REACh Regulation
print REACh Declaration
EU RoHS Directive Pro-active compliance (Product out of EU RoHS legal scope)
RoHS exemption information
print Yes
China RoHS Regulation
print China RoHS declaration
Take-back No
Carbon footprint (kg CO2 eq, Total Life cycle) 1